After-sales Service: | 1 Year |
---|---|
Warranty: | 1 Year |
Max Diameter of Workpiece: | <500mm |
Accuracy: | Cx: ±(read ×1%+1pF) tgδ: ±(read ×1%+0.00040) |
Anti interference: | Frequency conversion anti interference, under 200% interference, still can reach above accuracy. |
Capacitance range | Inner HV: 3pF~60000pF/10kV 60pF~1μF/0.5kv Outside HV: 3pF~1.5μF/10kV 60pF~30μF/0.5kV Resolution: Max. 0.001pF,4 significant figures |
Tgδ range: | unlimited, resolution:0.001%, capacitance, inductance, resistance can be identify automatically. |
Test current range: | 10μA~1A |
Inner HV | Setting voltage range: 0.5~10kV Max.Output current: 200mA Increase/decrease voltage: continuous slide regulating. Test frequency: 45, 50, 55 single frequency 45/55Hz auto double frequency conversion Frequency precision: ±0.01Hz |
Outside HV | Positive connection max. test current 1A, Power frequency or frequency conversion 40-70Hz Negative connection max. test current: 10kV/1A, power frequency or frequency conversion 40-70Hz |
CVT self excitation LV output: | voltage 3~50V,current 3~30A |
Measuring duty: | about 30s,it depend on measuring methods. |
Input power supply | 180V~270VAC,50Hz±1%,local supply or by generator. |
Communication interface: | RS232 |
Printer: | Build-in thermal printer. |
Environmental temperature: | -10ºC~50ºC |
Relative humidity: | <90% |
Oversize: | 463×362×350mm |
Weight | 29kg |